enLanguage
Oil Immersed Transformer
video

Oil Immersed Transformer

Rated Capacity: 50 kVA–2,500 kVA (higher capacity available) Voltage Class: 6 kV, 10 kV, 20 kV, 33 kV, 35 kV Frequency: 50 Hz / 60 Hz Phase: Three-phase or single-phase Cooling Type: ONAN, ONAF Insulation Medium: Mineral oil or ester fluid Winding Material: Copper or aluminum Standards: IEC 60076, IEEE C57 series Tap Changer: Off-circuit tap changer or OLTC Applications: Power distribution, industrial facilities, renewable energy projects, substations Testing: Routine tests according to applicable standards
Send Inquiry
Product Introduction

An oil immersed transformer transfers electrical power between different voltage levels while using insulating oil to provide electrical insulation and remove heat from the core and windings. In distribution systems, it is commonly used to reduce medium-voltage power to the low-voltage level required by industrial equipment, commercial facilities and local power networks.

 

Compared with dry-type transformers, oil immersed transformers are widely selected for outdoor installations and higher-capacity applications because the insulating oil provides both dielectric insulation and efficient heat dissipation. Depending on the project requirements, transformers can be configured for distribution or power applications with different voltage ratios, rated capacities, cooling methods and protection arrangements.

 

Octal Pipe provides oil immersed transformers with complete technical specifications matched to project requirements, covering transformer rating, voltage class, cooling arrangement, accessories, testing requirements and documentation. By selecting suitable configurations and coordinating supply requirements, Octal Pipe helps customers achieve a practical balance between technical requirements and project budget. The typical supply price range is USD 3,000 to 80,000 per unit (depending on rated capacity, voltage level, transformer configuration, winding material, cooling method and required technical options).

 

Oil Immersed Transformer Specifications

 

Oil immersed transformers are available in different voltage classes, capacity ranges and cooling configurations according to the power system requirements. The final design is determined by the rated capacity, voltage level, frequency, insulation system, cooling method and installation conditions.

 

Parameter Reference Configuration Specification Requirement
Rated capacity 30–2,500 kVA Select against maximum demand, load profile and planned expansion
Number of phases Three-phase Confirm the incoming supply and connected loads
Primary rated voltage 6, 6.3, 10, 10.5 or 11 kV State the required rated voltage and system conditions
Secondary rated voltage 0.4 kV Other secondary voltages require design confirmation
Rated frequency 50 Hz or 60 Hz Specify the frequency for which the transformer will be designed
Vector group Dyn11 or Yyn0 Confirm phase displacement and neutral requirements
Cooling ONAN for conventional naturally cooled designs State the rated capacity under the specified cooling conditions
Oil preservation Hermetically sealed or conservator arrangement Confirm the tank design and associated accessories
Winding conductor Copper or aluminium Identify the conductor material in the technical offer
HV tapping range ±5% or ±2×2.5% reference options Define the tap positions and tap-changer type
Short-circuit impedance Capacity- and design-specific Specify the required value, reference conditions and tolerance
No-load and load losses Model-specific guaranteed values Record the measurement conditions and applicable tolerances
Insulating liquid Mineral insulating oil for conventional designs Specify the oil grade and applicable requirements
Dimensions, total mass and oil quantity Model-specific Confirm against the approved general arrangement drawing

 

Transformer performance is defined by more than the rated capacity. Parameters such as vector group, short-circuit impedance, no-load loss, load loss and insulation level directly affect system compatibility, operating efficiency and protection coordination. These values are confirmed according to the transformer design, applicable standards and project requirements.

 

oil immersed transformer oil immersed distribution transformer,

 

Hermetically Sealed and Conservator Designs

 

The oil preservation system controls how the transformer manages the expansion and contraction of insulating oil during operation. Different tank designs are used depending on transformer capacity, installation conditions and maintenance requirements.

 

Design Construction and Oil Expansion Typical Application
Hermetically sealed The transformer tank is sealed from direct contact with ambient air. Oil expansion is accommodated through a corrugated tank wall, flexible expansion elements or a sealed gas space. Commonly used for compact distribution transformers where reduced oil oxidation and lower maintenance requirements are preferred.
Conservator type A conservator tank above the main transformer tank provides additional space for oil volume changes caused by temperature variation. Commonly used for larger transformers where oil monitoring, accessories and long-term service management are required.

 

Both designs are widely used for oil immersed transformers, with the selection depending on transformer capacity, operating environment and maintenance requirements.

 

The accessory arrangement is related to the selected tank design. Typical transformer accessories may include oil level indicators, temperature indicators, pressure relief devices, drain and sampling valves, Buchholz relays (for applicable conservator designs), alarms and protection contacts.

 

The final transformer configuration is determined according to the rated capacity, voltage level, cooling method, installation conditions and project technical requirements.

 

Oil-Filled Transformer Structure Conservator Type

Cooling and Voltage Regulation

 

ONAN means Oil Natural Air Natural. Oil circulates by natural convection, carrying heat from the active parts to the tank or radiators, where surrounding air removes it. The cooling process does not depend on externally driven oil circulation. 

 

The transformer's rated output must be assessed against its specified ambient conditions and cooling arrangement. Ventilation around the cooling surfaces matters, particularly where the transformer is installed inside an enclosure or building.

 

Voltage regulation requires a separate decision. A de-energized tap changer adjusts the winding ratio while the transformer is isolated and de-energized. An on-load tap changer is designed to change taps during operation. These arrangements have different equipment, control and maintenance requirements.

 

Voltage regulation is provided through a suitable tap changer configuration. A de-energized tap changer adjusts the winding ratio while the transformer is isolated and de-energized, while an on-load tap changer (OLTC) allows tap adjustment during operation. The selected tap range and operating method should match the system voltage variation requirements, and the transformer ratio and tap position are verified during factory testing.

Oil Immersed Transformer Cooling And Voltage Regulation

For detailed guidance on capacity selection, transformer configuration and RFQ requirements, refer to the Oil Immersed Transformer Selection Guide (PDF)

 

Losses, Impedance and Thermal Performance

 

Transformer efficiency and operating reliability are closely related to electrical losses, impedance characteristics and thermal performance. These parameters affect energy consumption, voltage stability, fault performance and the long-term operating condition of the transformer.

 

Performance Item Description
No-load loss Power loss generated in the transformer core when the transformer is energized without supplying load. It is mainly related to core material, magnetic flux density and core design.
Load loss Power loss occurring under load conditions, mainly caused by winding resistance and additional stray losses. It varies with the operating current of the transformer.
Short-circuit impedance The transformer impedance value expressed as a percentage of rated voltage and current. It affects voltage regulation, fault current characteristics and parallel operation capability.
Temperature rise The increase in oil and winding temperature during operation compared with the surrounding ambient temperature. It is controlled through the transformer design and cooling system.
Sound level The operating noise generated by the transformer core and electromagnetic effects, measured according to the specified test conditions.

 

For continuously energized transformers, no-load loss is present throughout the operating period, making it an important factor in lifetime energy consumption. For example, a 200 W reduction in no-load loss operating for 8,760 hours per year can reduce annual energy consumption by approximately 1,752 kWh.

 

The thermal capability of an oil immersed transformer is determined by the cooling arrangement, insulation system and applicable temperature-rise limits. According to IEC 60076-2, liquid-immersed transformers are evaluated through temperature-rise requirements and thermal performance tests to ensure suitable operation under the specified ambient conditions.

 

Manufacturing and Factory Testing

 

Transformer manufacturing combines magnetic-core preparation, winding production, insulation processing and tank assembly. Drying and oil handling require particular attention because moisture and contamination affect the insulation system.

 

Core preparation and winding manufacture → Active-part assembly → Controlled drying → Tank assembly → Oil processing and filling → Factory testing → Dispatch preparation

 

The drying and filling procedures must suit the insulation system and tank construction. Vacuum treatment should follow the approved manufacturing procedure and the tank's pressure capability.

 

Factory acceptance should be based on recorded results for the supplied equipment. The inspection schedule should require routine-test reports covering 100% of completed units, identified by serial number.

 

Inspection or Test Purpose Required Record or Acceptance Basis
Winding resistance Assess winding continuity and connections Recorded resistance, temperature and applicable tap positions
Voltage ratio and phase displacement Verify the specified ratio and connection Results against the approved vector group and tap schedule
No-load loss and current Verify excitation performance Measured values, test voltage and frequency
Load loss and short-circuit impedance Verify guaranteed electrical performance Results corrected to the agreed reference conditions
Applicable dielectric routine tests Verify insulation withstand performance Test method and levels selected under IEC 60076-3
Tank tightness testing Check the oil-containing assembly for leakage Procedure appropriate to the tank design and recorded result
Accessory and control checks Verify indications, contacts and auxiliary functions Checks against the approved accessory and wiring schedules

 

Ratio, winding-resistance and impedance measurements address different aspects of transformer condition; one successful test does not replace the others. Temperature-rise testing and other design-verification tests need a clearly agreed scope. Dielectric requirements vary with the winding and insulation category. Short-circuit withstand evidence may involve calculation, theoretical evaluation and special testing under IEC 60076-5; it should not be described as a destructive test routinely performed on every supplied unit. 

 

Standards and Technical Documentation

 

Oil immersed transformers are designed and tested according to applicable international standards covering transformer performance, insulation coordination, temperature rise, short-circuit capability and insulating oil quality. The applicable standard combination depends on the transformer type, voltage class, rated capacity and project requirements.

 

Standard Application Scope
IEC 60076-1 General requirements, ratings, service conditions and basic performance requirements for power transformers
IEC 60076-2 Temperature-rise limits and thermal performance tests for liquid-immersed transformers
IEC 60076-3 Insulation levels, dielectric tests and insulation coordination requirements
IEC 60076-5 Short-circuit withstand capability of transformers
IEC 60296 Requirements and test methods for mineral insulating oils used in electrical equipment

 

For each transformer project, the technical documentation package is prepared according to the approved configuration and includes key information such as transformer rating data, voltage ratio, vector group, cooling method, loss values, impedance, insulation level and accessory arrangement.

 

Each transformer is identified through its serial number, nameplate information and test records, allowing the delivered unit to be traced from factory production through final installation. For projects requiring third-party inspection, inspection points and document review requirements can be coordinated according to the project quality plan.

 

Applications and Site Requirements

 

Factory distribution and production-line expansion. A transformer feeding processing machinery, pumps or workshop equipment must suit the actual demand profile and the existing electrical system. Installation space, cable entry, neutral connections and protection coordination need checking alongside capacity.

 

Replacement within an existing substation. A replacement unit may have the correct kVA rating while still requiring changes to the foundation, busbar connections or cable terminations. The approved drawing should confirm overall dimensions, terminal positions, mass and handling arrangements before dispatch.

 

Remote and exposed installations. Outdoor projects may introduce high altitude, elevated ambient temperature, salt contamination or corrosive conditions. These conditions should be stated in the enquiry so the external insulation, cooling and protective finish can be assessed. Normal service conditions commonly use an altitude limit of 1,000 m; higher sites require specific consideration rather than an assumed standard rating. 

 

Facilities with continuous operation. Where the transformer remains energized throughout the year, loss guarantees and access for inspection deserve particular attention. Maintenance space and replacement access should be considered while the installation layout is still being developed.

 

Why Choose Octal Pipe

 

Octal Pipe supports oil immersed transformer supply by helping customers match the transformer configuration with their actual project requirements. Before supply, key parameters such as rated capacity, voltage ratio, cooling method, installation conditions and required standards are reviewed to avoid specification gaps during production and inspection.

 

For industrial and infrastructure projects, transformer supply often involves more than the main equipment. Octal Pipe coordinates related technical information, including datasheets, drawings, test reports, nameplate details and shipment documents, so that the delivered transformer can be checked against the approved project requirements.

 

Many transformer projects are integrated into existing power systems, where small differences in terminal arrangement, accessories or documentation can affect installation and commissioning. Maintaining clear technical communication from specification review to final delivery helps reduce these risks and supports smoother project execution.

 

Contact now

 

FAQ

 

 

product-470-408

01.Can oil immersed transformers operate in parallel?

Yes, when their voltage ratios, phase sequence, vector groups and impedances are compatible. Capacity and impedance relationships must also allow acceptable load sharing. Confirm compatibility against both units' technical data before connection.

02.Can a 50 Hz transformer be used on a 60 Hz supply?

The manufacturer must confirm suitability for the proposed voltage and frequency. Changing frequency affects magnetic flux and operating performance. A catalogue offering 50 Hz or 60 Hz designs does not mean every unit is interchangeable.

03.Can an oil filled transformer be installed indoors?

Yes, where the installation satisfies applicable electrical, fire and building requirements. Ventilation, oil containment, access and separation provisions must be assessed for the selected equipment and insulating liquid.

04.Does a hermetically sealed transformer require maintenance?

Yes. Sealing limits contact between the oil system and ambient air, but bushings, seals, connections, cooling surfaces and protective devices still require inspection under the manufacturer's maintenance instructions.

05.What is the service life of an oil immersed transformer?

There is no single guaranteed lifespan for all designs. Insulation condition, temperature, loading, moisture, faults and maintenance influence service life. Any stated design life should be accompanied by its operating assumptions.
Certifications

 

CE Certificate

CE Certificate

ISO 9001 Certificate

ISO 9001 Certificate

API Q1 Certificate

API Q1 Certificate

ABS Certificate

ABS Certificate

AP-5L Certificate

AP-5L Certificate

API-5CT Certificate

API-5CT Certificate

 

Hot Tags: oil immersed transformer, China oil immersed transformer manufacturers, suppliers, factory

Send Inquiry

whatsapp

Phone

E-mail

Inquiry